Goodrive300-01 inverter for air compressor Commissioning guidelines
-84-
S1
S3
S4
S5
S6
S7
COM
+24V
PW
AI1
PE
GND
AI2
RO2A
RO2C
RO1A
RO1C
S2
COM
A01
GND
485+
485-
ROA
ROC
AI
GND
485+
485-
S1
GND
R
S
T
R
S
T
Master inverter
U
V
W
U
V
W
R
S
T
Auxiliary power module
L
N
M
Main motor
M
Fan
PTB
PTA
PE
Air filter blocked
Oil filter blocked
Separator blocked
Fine separator blocked
External fault signal
Pressure
transmitter
Solenoid
valve coil
S8
Fan inverter
GD300-01
GD10/GD100
PP100
Master
inverter
OP
GND
485-
485+
COM
Y
Master
inverter
24V
GND
485-
485+
Touch
screen
Touch
screen
IoT module
485-
485+
R
S
T
PE
Temp detection signal
Voltage phase sequence detection signal
E-stop
Note:
a)
The one-key-to-set key is available once wiring is done according to above diagram.
b)
PT100 of GD300-01 in above diagram is selected by P18.03. It is set as temp detection terminal
(PTA, PTB and PTC) by default; temp transmitter can be set according to field needs
(P18.03=0), however, generally, temp transmitter needs no setup.
c)
Above wiring makes phase sequence detection function available, and users can set this
function on the touch screen as needed;
d)
In the internal 220V power of PP100, there is only 30W power can be used to supply solenoid
valve coil and contactor coil, please do not apply large-power load here.
e)
Please refer to Operation manual for PP100-01 air compressor power module on how to use
PP100 power module.
f)
Please refer to User manual for VT6070E series touch screen HMI on how to use the touch
screen