Goodrive300-01 inverter for air compressor Function parameters
-15-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
corresponds to the maximum frequency (P00.03) in
reverse direction.
Note: The pulse setting can only be input by
multi-function input terminals HDI. Set P05.00
(HDI input selection) to high-speed pulse input,
and set P05.49 (HDI high-speed pulse input
function selection) to frequency setting input.
5: Simple PLC program
The inverter runs at simple PLC program mode
when P00.06=5 or P00.07=5. Set P10 (simple PLC
and multi-step speed control) to select the running
frequency, running direction, ACC/DEC time and the
keeping time of corresponding step. See the function
description of P10 for detailed information.
6: multi-step speed running
The inverter runs at multi-step speed mode when
P00.06=6 or P00.07=6. Set P05 to select the current
running step, and set P10 to select the current
running frequency.
The multi-step speed has the priority when P00.06 or
P00.07 does not equal to 6, but the setting step can
only be the 1~15 step. The setting step is 0~15 if
P00.06 or P00.07 equals to 6.
7: PID control
The running mode of the inverter is procedure PID
control when P00.06=7 or P00.07=7. It is necessary
to set P09. The running frequency of the inverter is
the value after PID effect. See P09 for the detailed
information for the reference source, reference
value, and feedback source of PID.
8: MODBUS communication
The frequency is set by MODBUS communication.
See P14 for detailed information.
9: Reserved
10: Reserved
11: Reserved
P00.08
B frequency
command
reference
0: Maximum output frequency
100% of B frequency setting corresponds to the
maximum output frequency.
0
○