Goodrive300-01 inverter for air compressor Function parameters
-24-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
1: Output with voltage
2: Output at DC braking current at stopping
P02 Group Motor 1
P02.00
Motor type 1
0:Asynchronous motor
1:Synchronous motor
Note: Switch the current motor by the switching
channel of P08.31.
1
◎
P02.01
Rated power of
AM1
0.1~3000.0kW
Set the parameters of the
controlled asynchronous
motor.
To guarantee the control
performance, be sure to set
P02.01~P02.05 correctly
according to the name plate
of the motor.
The accuracy of parameter
autotuning for
Goodrive300-01 inverters
depends on correct setting of
motor parameters on the
name plate.
To guarantee the control
performance, configure the
motor as the standard motor.
If the motor power has a
great gap between the
standard, the control
performance of the inverter
will decrease obviously.
Note: Resetting the motor
rated power (P02.01) will
initialize P02.02~P02.05.
Depend
on model
◎
P02.02
Rated frequency
of AM1
0.01Hz~P00.03 (Max.
output frequency)
50.00Hz
◎
P02.03
Rated speed of
AM1
1~36000rpm
Depend
on model
◎
P02.04
Rated voltage of
AM1
0~1200V
Depend
on model
◎
P02.05
Rated current of
AM1
0.8~6000.0A
Depend
on model
◎
P02.06
Stator resistor of
AM1
0.001~65.535Ω
After motor parameter
autotuning, the settings of
P02.06~P02.10 update
automatically. As basic
parameters for high
performance vector control,
the parameters have a direct
Depend
on model
○
P02.07
Rotor resistor of
AM1
0.001~65.535Ω
Depend
on model
○
P02.08
Leakage
inductance of
AM1
0.1~6553.5mH
Depend
on model
○