Goodrive300-01 inverter for air compressor Safety precautions
-4-
1.4 Safety guidelines
Only qualified electricians are allowed to operate on the inverter.
Do not carry out any wiring, inspection or component replacement when the
power supply is applied. Ensure all input power supplies are disconnected before
wiring and inspection and always wait for at least the time designated on the
inverter or until the DC bus voltage is less than 36V. Below is the table of the
waiting time:
Inverter module
Minimum waiting time
380V
0.75kW-315kW
5 minutes
Do not refit the inverter unless authorized; otherwise fire, electric shock or other
injury may occur.
The base of the radiator may become hot during running. Do not touch to avoid
hurt.
The electrical parts and components inside the inverter are
electrostatic-sensitive. Take measurements to avoid electrostatic discharge
during relevant operation.
1.4.1 Delivery and installation
Please install the inverter on fire-retardant material and keep the inverter away
from combustible materials.
Connect the optional braking parts (braking resistors, braking units or feedback
units) according to the wiring diagram.
Do not operate on the inverter if damage or components missing occurred to
the inverter.
Do not touch the inverter with wet items or body, otherwise electric shock may
occur.
Note:
Select appropriate moving and installing tools to ensure a safe and normal running of the
inverter and avoid physical injury or death. For physical safety, the installer should take
some mechanical protective measures, such as wearing exposure shoes and working
uniforms.
Ensure to avoid physical shock or vibration during delivery and installation.
Do not carry the inverter by its front cover in case the cover falls off.
Install away from children and other public places.
The inverter cannot meet the requirements of low voltage protection in IEC61800-5-1 if the
altitude of installation site is above 2000m.
The inverter should be used in proper ambient environment
Prevent screws, cables and other conductive objects from falling into the inverter.
The leakage current of the inverter may exceed 3.5mA during operation. Ground with proper
techniques and ensure the grounding resistor is less than
10Ω. The conductivity of PE