Goodrive300-01 inverter for air compressor Function parameters
-46-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P06.18
Corresponding
AO1 output of
lower limit
output. When the output value exceeds the range of
set maximum or minimum output, it will count
according to the low-limit or upper-limit output.
When the analog output is current output, 1mA
equals to 0.5V.
In different cases, the corresponding analog output
of 100% of the output value is different.
10V (20mA)
0.0%
100.0%
AO
The setting range of P06.17: -100.0%~P06.19
The setting range of P06.18: 0.00~10.00V
The setting range of P06.19: P06.17~100.0%
The setting range of P06.20: 0.00V~10.00V
The setting range of P06.21: 0.000~10.000s
The setting range of P06.22: -100.0%~P06.24
The setting range of P06.23: 0.00~10.00V
The setting range of P06.24: P06.22~100.0%
The setting range of P06.25: 0.00~10.00V
The setting range of P06.26: 0.000~10.000s
P06.27~P6.31: Reserved
0.00V
○
P06.19
Upper output limit
of AO1
100.0%
○
P06.20
The
corresponding
AO1 output of
upper limit
10.00V
○
P06.21
AO1 output filter
time
0.000s
○
P06.22
Lower output limit
of AO2
0.0%
○
P06.23
Corresponding
AO2 output of
lower limit
0.00V
○
P06.24
Upper output limit
of AO2
100.0%
○
P06.25
The
corresponding
AO2 output of
upper limit
10.00V
○
P06.26
AO2 output filter
time
0.000s
○
P06.27
Reserved
●
P06.28
Reserved
●
P06.29
Reserved
●
P06.30
Reserved
●
P06.31
Reserved
●
P07 Group Human-machine interface
P07.00
User password
0~65535
The password protection will be valid when setting
any non-zero number.
00000: Clear the previous user password and make
the password protection invalid.
After the set user password becomes valid, if the
password is incorrect, users cannot enter the
0
○