INOVA AUTOMATION
NICE Series Integrated Elevator Solution
–
N Quick Start-Up Guide V1.0
80
Err 49
Err49
Door close fault
101: The consecutive times that the
door does not open to the limit
reaches the setting in Fb-13
101:
Check whether the door machine
system works properly.
Check whether the CTB is normal.
Check whether the door lock acts
properly.
5A
Err 50
Err50
Consecutive loss
of levelling signal
Levelling signal stuck or loss occurs
for three consecutive times (Err22 is
reported for three consecutive times).
101:
Check whether the levelling and door
zone sensors work properly.
Check the installation verticality and
depth of the levelling plates.
Check the levelling signal input points
of the MCB. Check whether the steel
rope slips.
5A
Err 53
Err53
Door lock fault
101: The door lock feedback signal
remains active for more than 3s
during door open.
102: The multiple door lock feedback
signal states are inconsistent for
more than 2s.
101:
Check whether the door lock circuit is
normal.
Check whether the feedback contact
of the door lock contactor acts
properly.
Check whether the system receives
the door open limit signal when the
door lock signal is valid.
102:
Check whether when the hall door
lock signal and the car door lock
signal are detected separately, the
detected states of the hall door locks
and car door lock are inconsistent.
5A
Err54
Err54
Overcurrent
at
inspection start-up
The current at start-up for inspection
exceeds 110% of the rated current.
101:
Reduce the load
Change Bit1 of FC-00 to 1 to cancel
the
start-up
current
detection
function.
5A
Err55
Err55
Stop at another
landing floor
101: During automatic running of the
elevator, the door open limit is not
achieved at the present floor.
101: Check the door open limit signal
at the present floor.
1A
Err57
Err57
Serial peripheral
interface
(SPI)
communication
abnormal
101, 102: The SPI communication is
abnormal. No correct data is received
with 2s of DSP communication.
103: The MCB does not match the AC
drive.
101, 102: Check the wiring between
the control board and the drive board.
103: Contact the agent or Monarch.
5A
Err58
Err58
Shaft
position
switches
abnormal
101: The up slow-down and down
slow-down
are
disconnected
simultaneously.
102: The up limit feedback and down
limit feedback are disconnected
simultaneously.
101, 102:
Check whether the states (NO, NC)
of the slow-down switches and limit
switches are consistent with the
parameter setting of the MCB.
Check whether malfunction of the
slow-down
switches
and
limit
switches occurs.
4B