INOVA AUTOMATION
NICE Series Integrated Elevator Solution
–
N Quick Start-Up Guide V1.0
34
6.3
Normal Operation & Its Signal Verification
Once the Door commissioning is completed, the lift is ready for normal operation
Turn ON the Inspection button into Normal model
Input signal status of Main Control Board (MCB) while the lift at top terminal floor level with doors are closed
in normal mode
If the Input Signal sequences are ok as per the requirement, then the lift can be run in normal speed.
Select the Normal running speed using the parameter F0-03
During Normal Operation, if Error53 comes, it is due to the improper door drive close and open limit feedback and
also due to presence of landing door and car door safety by-pass
Type of Input
Default
Input
Terminal
LED
status
Default
Parameter
Value
Default
Contact
Type
Remarks
Door Zone Switch signal
X1
ON
F5-01=003
NO
Running Contactor Feedback
(SW)
X2
ON
F5-02=104
NC
If
X2 LED off
, then the drive gives
Err36
while start
Brake Contactor Feedback (BY)
X3
ON
F5-03=105
NC
If
X3 LED off
, then the drive gives
Err37
always
Inspection mode input signal
X4
ON
F5-04=109
NC
OFF
INS mode
ON
Normal Mode
Inspection mode UP signal
X5
OFF
F5-05=010
NO
For UP direction command in INS
mode
Inspection mode DOWN signal
X6
OFF
F5-06=011
NO
For DOWN direction command in INS
mode
UP direction limit signal
X9
ON
F5-09=115
NC
Down direction limit signal
X10
ON
F5-10=116
NC
Up terminal slowdown signal
X11
OFF
F5-11=117
NC
As the Lift car is located at Top
Most Floor where the UP terminal
slowdown got activated
Down terminal slowdown signal
X12
ON
F5-12=118
NC
Over Load Feedback Signal
X13
ON
F5-13=119
NC
If Load cell is not available, keep F5-
13=0
Door Open Limit feedback
signal
X14
OFF
F5-14=022
NO
If DO limit signal is ‘NC’ contact,
keep F5-14=122
Door IR sensor signal
X15
ON
F5-15=126
NC
If Door IR sensor
feedback is ‘NO’,
keep F5-15=26
Door Close Limit Feedback
signal
X18
ON
F5-18=024
N0
If DC limit signal is ‘NC’ contact,
keep F5-14=124
Shorting Contactor Feedback
(FX)
X19
ON
F5-19=107
NC
Applicable for PMSM only
UPC contactor Feed back
X22
ON
F5-22=133
NC
Applicable for UPS ready ARD
function
Safety Circuit feedback signal
X25
ON
F5-25=01
NO
If all the field safety circuits are ok,
then the X25 LED gets
ON
Door lock safety circuit
feedback signal 1
X26
ON
F5-26=02
NO
If Car Door is safely closed, then
X26 LED gets
ON
Door lock safety circuit
feedback signal 1
X27
ON
F5-27=03
NO
If All landing doors are safely
closed, then X26 LED gets
ON