INOVA AUTOMATION
NICE Series Integrated Elevator Solution
–
N Quick Start-Up Guide V1.0
31
6.
Normal/High Speed Operation
6.1
Elevator Shaft Learning Process
Ensure that the hoist-way top and bottom
slowdown terminal, Direction Limit switches
and
floor level
magnetic plates or flags
are installed correctly before performing shaft self-learn.
Floor level switch cutting plates/flags (Door Zone)
Step 1:
Run the lift in Inspection mode and check the encoder pulse parameter F4-03 for pulse variation.
Pulse value
should
increase
when the lift runs in
UP direction
and
decrease
when the lift runs in
Down
direction
If
pulse variation is reverse
, then modify the parameter
F2-10 (0
↔1)
Make sure that the all required mechanical installation and field wiring are completed. Take the lift to bottom
terminal floor level using control panel Inspection in inspection speed
Observe the X1~X24 input terminal LEDs for proper operation of
Floor/Door zone(X1 LED)
and
Up/Down
terminal Limit and slowdown switches(X09,X10,X11 & X12 LEDs)
Locate the lift car in bottom most floor level, Down terminal Slowdown switch gets operated
(X12 ‘OFF’)
and
Floor level/Door Zone Switch (F5-01=003) gets operated
(X1 ‘ON’)
Step 2:
Set the following parameters
Description
Parameter code
Default Value
New Value
Remarks
Highest Floor
F6-00
5
Enter the total number of floor (no.
of opening)
Lowest Floor
F6-01
1
1
Step 3:
Now select the parameter
F1-11=3(Shaft auto learning mode)
and
Enter
or
Keep Pressing ‘
S1’
button located on MCTC-MCB of NICE 1000+ for minimum 3secs
Floor/Door zone switch
mounted on Car-top
Floor/Door zone switch
cutting plates/flags
(80mm)
fixed on shaft Guide rail
Shaft Auto learning
enable switch (S1)