Installation and Programming Manual
Installation
19
Chapter 3
INSTALLATION
3-1
Installing the control panel
3-1-1
Wall-mounting
The control panel should be located in a hidden place that can be accessed by
authorized building occupants only.
1. Using the backbox (
Table 4: Control panels - description of parts, G
), mark
the anchor screw locations on the wall. Be sure not to drill in the vicinity of
electrical wiring or plumbing/gas pipes, etc.
2. Insert the screw anchors (recommended size 6mm).
3. Pull the wires through the wire entry.
4. Using the screws, attach the backbox to the wall.
5. Fit the dislodgement-tamper microswitch (provided with SmartLiving
1050L and 10100L, optional for SmartLiving 505, 515 and 1050, refer to
Appendix H, Order Codes, TamperNO
).
5.1. Insert the dislodgement-tamper bracket [A] into its location on the
backbox of the control panel (
Table 4: Control panels - description of
parts, H
).
5.2. Using screw location [B], screw the bracket to the wall.
5.3. Connect the wire coming from the dislodgement-tamper microswitch [C] to
the connector [D] on the board (
Table 4: Control panels - description of
parts, T
).
Note
The sleeving must be flame class rating V-1 or higher.
3-1-2
Connecting the Mains
power supply
The control panel must be powered through a separate line coming from the
Mains box. The line must be protected by a safety-standards compliant circuit
breaker (trip switch).
The circuit breaker (trip switch) must be located externally to the apparatus and
should be easily accessible. The distance between contacts must be at least
3mm. The manufacturer strongly advises the use of a magnetothermic switch
with C intervention curve and nominal (maximum) current - 16A.
The protective earthing system must be compliant with all safety standards and
laws in force.
DANGER!
Ensure that the Mains is switched Off during the mains connection phase. Danger
of electric shock.
The 505 and 515 models
Pull the mains (primary power-supply) cable through the cable entry [B], then
complete the (Mains) connections on the mains terminal board [A]. When
connecting the earth wire, follow the indications on the label [C] located near the
mains terminal board. The transformer (located above the PCB) and switching
power supply (housed inside the control panel enclosure) provide the power
source to the entire system and supply the charge voltage to the backup battery.
The 1050, 1050L and 10100L models
Pull the cable through the cable entry [E], then connect the mains power to the
power-supply terminal board [D], located on the backplate above the
motherboard. When connecting the earth wire, follow the indications on the
power-supply label [F]. The power-supply provides power to the system and
supplies the charge voltage.
A
B
C
D
C
E
F
N
L
MAIN FUSE T
500mA L250V
AC
Input
A
B
C
SmartLiving 505/515