GENERAL INFORMATION
18
SL, SM & SH 90, 110, 132, 150, 200, 250 &300 (50Hz)
L, H & HH 125, 150, 200, 250, 300, 350 & 400 (60Hz)
CCV
CONDENSATE CHECK VALVE
1SV
LOAD SOLENOID VALVE
6SV
INTERSTAGE CONDENSATE SOLENOID VALVE
9SV
DISCHARGE CONDENSATE SOLENOID VALVE
CLS
CONDENSATE LEVEL SWITCH (OPTIONAL)
1AVPT
VACUUM PRESSURE TRANSDUCER RANGE : 0–1 BAR
(0–15psi)
2APT
AIR PRESSURE TRANSDUCER RANGE : 0–6.9 BAR
(0–100psi)
3APT
AIR PRESSURE TRANSDUCER RANGE : 0–13.8 BAR
(0–200psi)
4APT
AIR PRESSURE TRANSDUCER RANGE : 0–13.8 BAR
(0–200psi)
50PT
OIL PRESSURE TRANSDUCER RANGE : 0–6.9 BAR
(0–100psi)
60PT
OIL PRESSURE TRANSDUCER RANGE : 0–6.9 BAR
(0–100psi)
2ATT
AIR TEMPERATURE TRANSDUCER (RTD) RANGE :
–18
+
266
°
C (0–510
°
F)
3ATT
AIR TEMPERATURE TRANSDUCER (THERMISTOR)
RANGE : –18
+
121
°
C (0–250
°
F)
4ATT
AIR TEMPERATURE TRANSDUCER (RTD) RANGE :
–18
+
266
°
C (0–510
°
F)
7ATT
AIR TEMPERATURE TRANSDUCER (THERMISTOR)
RANGE : –18
+
121
°
C (0–250
°
F)
50TT
OIL TEMPERATURE TRANSDUCER (THERMISTOR)
RANGE : –18
+
121
°
C (0–250
°
F)