background image

MAINTENANCE

64

SL, SM & SH 90, 110, 132, 150, 200, 250 &300 (50Hz)
L, H & HH 125, 150, 200, 250, 300, 350 & 400 (60Hz)

WARNING

Do not under any circumstances open any drain valve or remove

components from the compressor without first ensuring that the
compressor is FULLY SHUT–DOWN, power isolated and all air
pressure relieved from the system.

AIR FILTER CHANGE PROCEDURE

A warning message will appear if the air filter pressure drop exceeds

0,048 bar (0,7 psi). To check the condition of the inlet filter, run the
compressor in load mode and select “INLET VACUUM” from the
current status screen using the up and down arrows. Change if equal
to or above 0,048 bar (0,7 psi). To change the inlet filter, remove the
appropriate enclosure panel on the front of the machine. Unscrew the
wingnut and remove the cover to expose the filter. Remove the dirty
filter. Clean all interior surfaces of the filter box as required. Install new
filter element(s). Replace cover and tighten wingnut. Re–install
enclosure panel. Start machine and run in the load mode to verify filter
condition

Parts required

Air filter element
S90

qty 1.

S110/S132/S150

qty 2

HIGH DUST OPTION :

To change inlet filter element, remove the right front enclosure

panel, loosen the wingnut on the end of the filter housing. Remove the
primary element.

NOTE: the safety element should be changed every other primary

element change. If safety element service is required, remove it at this
time.

With the elements removed, inspect the vacuator valve to see that

it is not inverted, damaged or unplugged. repair or replace it as
necessary. Clean the gasket sealing surfaces of the filter housing.
Inspect all filter connections and compressor inlet ducting for a leak
tight fit. Carefully install each new element and wingnuts. Reinstall
enclosure panel.

Start machine and run in load mode to verify filter condition.

OIL AND OIL FILTER

Change oil filter after every 8,000 hours or less as required (see

checking procedure below).To check the condition of the oil filter, the
compressor must be running and the oil temperature must be greater
than 49

_

C (120

_

F). With these conditions met select ”OIL FILTER

PRESS DROP” from current status screen. If ”OIL FILTER PRESS
DROP  is less than 0,9 bar (13 psi) then the oil and filter do not need
service. If the warning light is on and ”CHANGE OIL FILTER” warning
is displayed, then the oil should be drained and the filter replaced.

To change the oil and filter, the oil should be warm for more effective

drainage. Remove the right end enclosure panel. Remove the pipe plug
from the oil drain connection in the rear of the baseplate. Place a
suitable drain pan under the drain connection and open the valve.

Dispose of waste lubricant according to local regulations.

When the gearcase is empty, close the valve and replace the pipe

plug. Position the empty drain pan under the oil filter. Remove the filter
and allow the oil to drain from the oil cooler as well. Wipe the sealing
surface of the filter adaptor with a clean, lint–free cloth. Remove the
replacement filter from its protective package. Apply a small amount of
clean oil on the rubber seal and install the element. Screw the element
on until the seal makes contact with the seat on the adaptor head.
Tighten the filter a further 1/2 to 3/4 of a turn.

Unscrew the oil filler cap and add oil until the level reaches the top

of the gearcase sight glass.

Start the compressor and run in unload mode. Check the oil filter

and oil drain valve for leaks. Select ”BEARING OIL PRESS” from the
current status screen to insure that adequate oil pressure has been
attained. Inspect the gearcase sight glass, the correct oil level for the
sump during operation is 

3

/

4

 to 

4

/

full. Some amount of foaming in the

sight glass is normal. The oil level is interpreted as the level in the sight
glass below the top foam, where a line of separation can be seen. If
additional oil is required, stop the compressor and add oil as needed.

Tools required

Wide–blade screwdriver or 3/8” wrench or 3/8” socket with ratchet
400mm adjustable wrench
600mm adjustable wrench
Oil filter wrench

Parts required

Oil filter element
Approximately 49 litre (13 U.S. gall) of I–R ULTRA COOLANT
hydraulic oil.
(90–150kW/125–200HP)
Approximately 91 litre (24 U.S. gall) of I–R ULTRA COOLANT
hydraulic oil.
(200–300kW/250–400HP)

GEARCASE BREATHER

To service the gearcase breather, remove the right end panel

.

Remove the breather cover by unscrewing the four retaining screws.
Remove all of the breather media and clean with a suitable solvent.
Allow the media to dry. Re–install the media, the cover, and the
enclosure panel.

CONDENSATE DRAIN FUNCTIONALITY

To verify the functionality of the condensate drains, simply observe

the timed operation of each. Each drain should open at least every 2
minutes while the compressor is loaded. (The intercooler drain
exhausts at a much lower pressure than the aftercooler).

Oil free condensate can be disposed of via a sewer drain.

CONDENSATE STRAINERS

In order to service the condensate strainers (both interstage and

discharge), the strainer service valves preceding the strainers should
be closed. Remove the screens from the strainers, while noting the
direction. Clean any debris from the screens and reinstall. Open the
strainer service valves.

AIREND BEARINGS

Airend bearings are lubricated by the compressor lubricating oil and

require no maintenance.

COMPRESSOR MODULE INPUT SHAFT SEAL REPLACEMENT

1. Remove the main motor, observing all safety precautions in Section
A of this manual, utilising appropriate lifting gear as recommended and
following established safe working practices.

2. Pull the compressor coupling half off the shaft.

3. Remove the 4 bolts retaining the seal housing and screw 2 of them
to remove the housing complete with seal.

4. Remove the old seal from the housing.

5. Remove the old wear sleeve from the input shaft.

6. Clean the seal housing, input shaft, wear sleeve inside diameter and
seal outside diameter (Absolutely grease free).

Summary of Contents for Sierra H 125

Page 1: ...information and must be made available to personnel who operate and maintain this machine OPERATION AND MAINTENANCE MANUAL LIBRO D USO E MANUTENZIONE MANUAL DE MANEJO Y MANTENIMIENTO MANUAL DE OPERA...

Page 2: ......

Page 3: ...l surfaces welds and fittings report any excessive corrosion mechanical or impact damage report any leakage or other deterioration 6 year Remove lid and any necessary fittings Fully clean out Fully in...

Page 4: ......

Page 5: ...to Serial No From Serial No Not illustrated Option NR Not required AR As required SM Sitemaster Sitepack HA High ambient machine WC Watercooled machine AC Aircooled machine ERS Energy recovery system...

Page 6: ...Rand has no control Therefore Ingersoll Rand does not accept any liability for losses caused by equipment in which non approved repair parts are installed Standard warranty conditions may be affected...

Page 7: ...Mandatory Information Instructions Warning Use fork lift truck from this side only RESET Do not use fork lift truck from this side Emergency stop On power Off power AUTOMATIC RESTART MAINTENANCE MAIN...

Page 8: ...DECALS 4 SL SM SH 90 110 132 150 200 250 300 50Hz L H HH 125 150 200 250 300 350 400 60Hz CHANGE REPLACE CLEAN POWER INLET AC Pinch point hazard Keep hands clear...

Page 9: ...anual WARNING Do not undertake any maintenance on this machine until the electrical supply is disconnected and the air pressure is totally relieved WARNING Consult the operation and maintenance manual...

Page 10: ...the machine without the guard being fitted Do not stand on any service valve or other parts of the pressure system Do not operate with the doors or enclosure open Do not use fork lift truck from this...

Page 11: ...L SM SH 90 110 132 150 200 250 300 50Hz L H HH 125 150 200 250 300 350 400 60Hz Air intake Minimum clearance to walls Use only Ingersoll Rand ULTRA COOLANT lubricating oil Oil pressure Air pressure Fi...

Page 12: ...DECALS 60Hz 8 SL SM SH 90 110 132 150 200 250 300 50Hz L H HH 125 150 200 250 300 350 400 60Hz...

Page 13: ...DECALS 60Hz 9 SL SM SH 90 110 132 150 200 250 300 50Hz L H HH 125 150 200 250 300 350 400 60Hz...

Page 14: ...DECALS 60Hz 10 SL SM SH 90 110 132 150 200 250 300 50Hz L H HH 125 150 200 250 300 350 400 60Hz...

Page 15: ...eved at the process vent point external to the compressor Ensure that the machine is operating at the rated pressure and that the rated pressure is known to all relevant personnel All air pressure equ...

Page 16: ...nes when in use are kept at least 5 metres from the perimeter of a machine which is operatingor is being worked on whilst connected to its power supply Condensate disposal As waste water regulations v...

Page 17: ...FILTER BFV BUTTERFLY THROTTLE VALVE HC HYDRAULIC CYLINDER IC INTERCOOLER AC AFTERCOOLER OC OIL COOLER OM OIL MANIFOLD OF OIL FILTER OTCV OIL TEMP CONTROL VALVE OP OIL PUMP ODV OIL DRAIN VALVE 1OR ORIF...

Page 18: ...1SV LOAD SOLENOID VALVE 6SV INTERSTAGE CONDENSATE SOLENOID VALVE 9SV DISCHARGE CONDENSATE SOLENOID VALVE CLS CONDENSATE LEVEL SWITCH OPTIONAL 1AVPT VACUUM PRESSURE TRANSDUCER RANGE 0 1 BAR 0 15psi 2AP...

Page 19: ...HC HYDRAULIC CYLINDER IC INTERCOOLER AC AFTERCOOLER OC OIL COOLER OM OIL MANIFOLD OF OIL FILTER OTCV OIL TEMP CONTROL VALVE OP OIL PUMP ODV OIL DRAIN VALVE 1OR ORIFICE BLOWDOWN 2OR ORIFICE OIL FLOW OS...

Page 20: ...SOLENOID VALVE 4SV WATER SOLENOID VALVE WVV WATER VENT VALVE CLS CONDENSATE LEVEL SWITCH OPTIONAL 1AVPT VACUUM PRESSURE TRANSDUCER RANGE 0 1 BAR 0 15psi 2APT AIR PRESSURE TRANSDUCER RANGE 0 6 9 BAR 0...

Page 21: ...IL STRAINER BR BREATHER BDV BLOWDOWN VALVE DCV DISCHARGE CHECK VALVE CA COMPRESSED AIR C CONDENSATE 1DS FIRST STAGE DISCHARGE SILENCER 2DS SECOND STAGE DISCHARGE SILENCER 3DS BLOWDOWN DISCHARGE SILENC...

Page 22: ...ANGE 0 6 9 BAR 0 100psi 3APT AIR PRESSURE TRANSDUCER RANGE 0 13 8 BAR 0 200psi 4APT AIR PRESSURE TRANSDUCER RANGE 0 13 8 BAR 0 200psi 50PT OIL PRESSURE TRANSDUCER RANGE 0 6 9 BAR 0 100psi 60PT OIL PRE...

Page 23: ...VALVE CW COOLING WATER CA COMPRESSED AIR C CONDENSATE 1DS FIRST STAGE DISCHARGE SILENCER 2DS SECOND STAGE DISCHARGE SILENCER 3DS BLOWDOWN DISCHARGE SILENCER 1EJ INTERSTAGE EXPANSION JOINT 2EJ DISCHARG...

Page 24: ...GE 0 13 8 BAR 0 200psi 4APT AIR PRESSURE TRANSDUCER RANGE 0 13 8 BAR 0 200psi 50PT OIL PRESSURE TRANSDUCER RANGE 0 6 9 BAR 0 100psi 60PT OIL PRESSURE TRANSDUCER RANGE 0 6 9 BAR 0 100psi 2ATT AIR TEMPE...

Page 25: ...ions A wafer type check valve is provided to prevent any backflow of air into the compressor The aftercooler cools the air to a suitable temperature while the discharge moisture separator removes sign...

Page 26: ...tart warning message will appear in the display to indicate the compressor has shut down automatically and will restart automatically An automatic restart will occur when the line pressure drops to th...

Page 27: ...given before restart SEQUENCER CONTROL Sequencer control capability can be added to the electronic control system by utilising a sequencer interface This option is available as a field installation k...

Page 28: ...Earth lead Main terminal E1 Earth lead Back panel E2 Earth lead motor E3 Earth lead sub base E4 Earth lead RFI filter E5 Earth lead Fan motor E6 Earth lead Control transformers E7 Earth lead Starter...

Page 29: ...rt option optional CLS Switch interstage condensate level optional CON Intellisys controller GA Remote alarm contacts RSP Remote stop RST Remote start RLL Remote lead lag switch RLE Remote load enable...

Page 30: ...ling air exhaust C Air intake D Starter box E 1 BSPT Breather piping connection F 1 2 BSPT Aftercooler solenoid condensate drain G 1 4 BSPT Aftercooler manual condensate drain H 1 4 BSPT Intercooler m...

Page 31: ...discharge location 9 There should be no plastic or PVC piping attached to this unit or used for any lines downstream 10 Forklift hole covers must be installed after unit is in place to reduce noise a...

Page 32: ...Air intake D Starter box E 1 BSPT Breather piping connection F 1 2 BSPT Aftercooler solenoid condensate drain G 1 4 BSPT Aftercooler manual condensate drain H 1 4 BSPT Intercooler manual condensate d...

Page 33: ...on 9 There should be no plastic or PVC piping attached to this unit or used for any lines downstream 10 Forklift hole covers must be installed after unit is in place to reduce noise and insure proper...

Page 34: ...area B Cooling air exhaust C Air intake D Starter box E 1 NPT Breather piping connection F 1 2 NPT Aftercooler solenoid condensate drain G 1 4 NPT Aftercooler manual condensate drain H 1 4 NPT Interc...

Page 35: ...discharge location 9 There should be no plastic or PVC piping attached to this unit or used for any lines downstream 10 Forklift hole covers must be installed after unit is in place to reduce noise an...

Page 36: ...r exhaust C Air intake D Starter box E 1 NPT Breather piping connection F 1 2 NPT Aftercooler solenoid condensate drain G 1 4 NPT Aftercooler manual condensate drain H 1 4 NPT Intercooler manual conde...

Page 37: ...ion 9 There should be no plastic or PVC piping attached to this unit or used for any lines downstream 10 Forklift hole covers must be installed after unit is in place to reduce noise and insure proper...

Page 38: ...ce area B Cooling air exhaust C Air intake D Fork lift truck channels E 4 ANSI Flange air discharge F 1 BSPT Breather piping connection G Seal vent opening do not plug H 1 2 BSPT Intercooler condensat...

Page 39: ...unit is in place to reduce noise and insure proper cooling of package 11 Field installed ducting to and from compressor cannot add more than 6mm 0 25 inches of water total air resistance Gear box bre...

Page 40: ...e area B Cooling air exhaust C Air intake D Fork lift truck channels E Starter box F 1 BSPT Breather piping connection G Seal vent opening do not plug H 1 2 BSPT Intercooler condensate drain J 1 4 BSP...

Page 41: ...for any lines downstream 10 Forklift hole covers must be installed after unit is in place to reduce noise and insure proper cooling of package 11 Field installed ducting to and from compressor cannot...

Page 42: ...r clearance area B Cooling air exhaust C Air intake D Fork lift truck channels E 4 ANSI Flange air discharge F 1 NPT Breather piping connection G Seal vent opening do not plug H 1 2 NPT Intercooler co...

Page 43: ...installed after unit is in place to reduce noise and insure proper cooling of package 11 Field installed ducting to and from compressor cannot add more than 6mm 0 25 inches of water total air resista...

Page 44: ...rance area B Cooling air exhaust C Air intake D Fork lift truck channels E Starter box F 1 NPT Breather piping connection G Seal vent opening do not plug H 1 2 NPT Intercooler condensate drain J 1 4 N...

Page 45: ...ownstream 10 Forklift hole covers must be installed after unit is in place to reduce noise and insure proper cooling of package 11 Field installed ducting to and from compressor cannot add more than 6...

Page 46: ...o move the machine Alternatively a special lifting frame can be supplied to enable a crane or hoist to move the compressor Ensure that the correct fork lift truck slots or marked lifting tie down poin...

Page 47: ...oints in the piping systems should be provided with driplegs and traps CAUTION Do not use the compressor to support the discharge pipe It is essential when installing a new compressor 1 to review the...

Page 48: ...n a cooling system show up first in a reduction in the heat transfer rate then in a reduced flow rate and finally with damage to the system There are many constituents in the water system that must be...

Page 49: ...check for correct rotation FAN MOTOR Observe the compressor cooling fan The rotation should be in accordance with the fan rotation decal affixed to the fan motor Cooling air should exhaust from the to...

Page 50: ...13 60 13 00 19 40 18 00 15 30 22 80 21 40 18 80 25 90 24 60 22 10 CAPACITY ft3 min 560 479 458 683 635 542 804 756 664 913 869 782 FULL LOAD CURRENT MAXIMUM 380V A 207 251 299 340 FULL LOAD CURRENT MA...

Page 51: ...35 00 32 62 27 41 45 23 41 52 35 47 43 32 CAPACITY ft3 min 1236 1152 968 1597 1466 1253 1530 FULL LOAD CURRENT MAXIMUM 380V A 431 536 653 FULL LOAD CURRENT MAXIMUM 415V A 426 517 591 STARTING CURRENT...

Page 52: ...13 60 13 00 19 40 18 00 15 30 22 80 21 40 18 80 25 90 24 60 22 10 CAPACITY ft3 min 560 479 458 683 635 542 804 756 664 913 869 782 FULL LOAD CURRENT MAXIMUM 380V A 207 251 299 340 FULL LOAD CURRENT MA...

Page 53: ...35 00 32 62 27 41 45 23 41 52 35 47 43 32 CAPACITY ft3 min 1236 1152 968 1597 1466 1253 1530 FULL LOAD CURRENT MAXIMUM 380V A 431 536 653 FULL LOAD CURRENT MAXIMUM 415V A 426 517 591 STARTING CURRENT...

Page 54: ...n 16 6 14 8 13 5 19 6 19 6 16 0 25 8 24 2 21 5 CAPACITY ft3 min 585 523 477 690 690 565 911 854 759 FULL LOAD CURRENT MAXIMUM 460V A 178 214 260 FULL LOAD CURRENT MAXIMUM 575V A 142 165 208 STARTING C...

Page 55: ...9 59 35 79 31 49 45 31 42 51 37 66 43 24 CAPACITY ft3 min 1182 1070 905 1398 1264 1112 1600 1501 1330 1527 FULL LOAD CURRENT MAXIMUM 460V A 387 351 396 464 FULL LOAD CURRENT MAXIMUM 575V A 310 281 318...

Page 56: ...16 6 14 8 13 5 19 6 19 6 16 0 25 8 24 2 21 52 CAPACITY ft3 min 585 523 477 691 691 565 912 855 760 FULL LOAD CURRENT MAXIMUM 460V A 168 193 246 FULL LOAD CURRENT MAXIMUM 575V A 134 155 197 STARTING C...

Page 57: ...23446 23446 26863 Equivalentcontinuous sound pressure level workstation rated load ELECTRICAL DATA An independent electrical isolator should be installed adjacent to the compressor Feeder cables shoul...

Page 58: ...o unload and remain unloaded The display will indicate that the machine is RUNNING UNLOADED and MODE UNLOAD LOAD 6 Pressing this button will cause the compressor to load if the compressor is running a...

Page 59: ...corner of the screen indicate when you can move up designated by arrow head pointing up and or down designated by arrow head pointing down through a list The arrow buttons are also used to change an i...

Page 60: ...ter the value Depressing Cancel will exit the edit mode and leave the value unchanged Depressing Set will save the new value and flash the value to indicate acceptance 4 Depressing Cancel will exit th...

Page 61: ...T SETPOINTS Lead Lag Lead Lag Lead Offline 60 to 1 psig Pressure RATED 3 Lead Online 50 to 1 psig Pressure OFFLINE 10 Lag offset 0 to 45 1 psig Load Delay Time 0 to 60 1 SEC Condensate interval 60 to...

Page 62: ...n item s value can be changed the same way that OPERATOR SETPOINTS values are changed denotes alternative units for reference SENSOR CALIBRATION 6 90 bar 100 psi SENSOR CALIBRATION CALIBRATE READY TO...

Page 63: ...100 psi PACKAGE DISCH PRESSURE 13 7 bar 198 psi READY TO START PACKAGE DISCHARGE TEMP 40_C 104_F STATUS MAIN MENU ALARM HIST The name and value of each of the items listed below can be seen by moving...

Page 64: ...LINE PRESS RESET TWICE STATUS MAIN MENU RESET ALARMS When an Alarm occurs the word ALARM will flash on the display screen and appear in large letters as shown above The display message will indicate w...

Page 65: ...Motor Overload Occurs if a fan motor overload relay contact opens Remote Stop Failure Occurs if the REMOTE START STOP option is enabled the remote stop button remains open and either start button is p...

Page 66: ...in a hazardous position 6 Ensure that the electric motor and electrical equipment has not become exposed or saturated with moisture water See installation section DECOMMISSIONING When the machine is...

Page 67: ...ENERAL INFORMATION section of this manual Compressed air can be dangerous if incorrectly handled Before doing any work on the unit ensure that all pressure is vented from the system and that the machi...

Page 68: ...oil to drain from the oil cooler as well Wipe the sealing surface of the filter adaptor with a clean lint free cloth Remove the replacementfilter from its protective package Apply a small amount of c...

Page 69: ...the end of the installation tool while the seal leaves the tool and enters the wear sleeve The seal will slip between the tool and the sleeve if pressure is not applied 14 Apply Loctite 242 to the 4 s...

Page 70: ...m Verify that 2nd stage discharge temperature in the unload reduces slowly from the temperature in the load mode If the unload temperature is greater adjust the inlet unloading valve Note The inlet va...

Page 71: ...to clear Calibrate sensors Check all set points CK CONTROL PWR PHASE Check phase monitor Check fuses Check transformer and wiring connections REMOTE STOP FAILURE Check remote stop switch and wiring RE...

Page 72: ...and clean AFTERCOOLER CORE DIRTY Inspect and clean ENCLOSURE PANELS NOT IN PLACE Install enclosure panels NO AFTERCOOLER ON UNIT Install aftercooler DRAIN LINE DRIP LEG INCORRECTLY INSTALLED Slope dr...

Reviews: