OPERATING INSTRUCTIONS
58
SL, SM & SH 90, 110, 132, 150, 200, 250 &300 (50Hz)
L, H & HH 125, 150, 200, 250, 300, 350 & 400 (60Hz)
[ ] denotes alternative units for reference.
–OPTIONS–
#
6,90
bar
[100]
[psi]
AUTO RESTART
OFF
READY TO START
AUTO RESTART TIME
2–15 MINUTES
STATUS
MAIN MENU
SELECT
OPTIONS
Options are turned on or off and their associated values are set
using the OPTION screen.
Some options require additional machine hardware and the correct
“Option Module” to plug into the INTELLISYS controller. The name and
value of each of the following options can be seen by moving the list up
and down using the arrow buttons.
OPTIONS Items
Range
Step
Unit
Auto Restart Time
2 to 15
1
min
Auto Restart
YES/NO
–
–
Sequencer
YES/NO
–
–
Remote Start/Stop
YES/NO
–
–
*Power Out Restart YES/NO
–
–
*Power Out Restart 10 to 120
1
sec
Time
Cond. Level
YES/NO
–
–
Installed
Lead / Lag
0–750
1
Hour
Cycle Length
*Scheduled
00:00–23:59
–
Hr : Min
Start
*Scheduled
00:00–23:59
–
Hr : Min
Stop
*Require an option module to be added to the controller.
An
Option
item’s value can be changed the same way that
OPERATOR SETPOINTS values are changed.
[ ] denotes alternative units for reference.
–SENSOR CALIBRATION–
#
6,90
bar
[100]
[psi]
–SENSOR CALIBRATION–
CALIBRATE
READY TO START
SENSOR 3APT
CALIBRATE
STATUS
MAIN MENU
SELECT
SENSOR CALIBRATION
Pressure sensor calibration is done through the SENSOR
CALIBRATION screen. Sensor calibration can only take place when
the machine is stopped and isolated from the compressed air system
and fully depressurised (otherwise, 4APT will fail because it is still
on–line to the system). Calibration needs to be done only after a sensor
has been replaced or the INTELLISYS controller has been replaced.
Each of the sensors listed below can be chosen by using the up and
down arrow buttons to highlight it on the screen.
SENSOR CALIBRATION Items
Sensor 1AVPT
(Inlet Vacuum)
Sensor 2APT
(2nd Stage Inlet)
Sensor 3APT
(2nd Stage Discharge)
Sensor 4APT
(Package Discharge)
Sensor 5OPT
(Oil Filter In)
Sensor 6OPT
(Bearing Oil)
Select the highlighted sensor by pressing the SELECT button.
Press the CALIBRATE button to start the automatic calibration
procedure, or press the CANCEL button to not calibrate it and return
to the sensor list.