Everest XCR - Product manual |
Wiring and Connections
INGENIA | 2020-10-01 00:04:38
48
Safety Function
Specification
Value
High-demand
mode
The EUC (Equipment Under Control) is considered as a high-demand or continuous demand
mode system.
Mission Time
The mission time of the EUC is of 20 years.
Diagnostic
Time Interval
In order to guarantee the correct operation of the safety functions, the user has to check the
STO function regularly, performing an STO External Diagnostic Test (see further information
below).
The diagnostic test interval is defined as a minimum of 1 activation per 3 months.
9.4.2. Integration Requirements
Integration
Requirement
Value
STO Interface
electrical
characteristics
Input pins
STO1, STO2 and STO_RET
Number of
independent
channels
2
Type of Inputs
Isolated inputs (STO1, STO2) with common reference (STO_RET).
ESD protected with input current limit to reduce power. See
schematics next.
Maximum input LOW
level (VIL)
1.1 V or open (below this value the STO is ACTIVE, no torque can be
applied to the motor)
Minimum Input HIGH
level (VIH)
3.6 V (above this value the STO input is inactive, torque can be applied
to the motor)
Maximum absolute
ratings
24 V SELV (maximum OVP 26.4V (110%); maximum failure voltage 60
V)
Input current
5 mA typ / 10 mA max
Isolation Level
> 4 G
Ω
, 500 V
rms
, 1000 V
DC
ESD capability
IEC 61000-4-2 (ESD) ± 15 kV (air), ± 8 kV (contact), IEC 61000-4-4 (EFT)
40 A (5/50 ns), IEC 61000-4-5 (Surge) IPPM > 8 A
STO Interface
timing
characteristics
STO activation time
(Safety function
Reaction Time)
t < 6.3 ms
STO deactivation
time
t < 2ms