ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Error description
AS-I system errors: error codes E10...E32
242
16.2
AS-I system errors: error codes E10...E32
Error message appears instead of the start screen.
No interruption of the menu operation.
Exclamation mark flashes in the text/graphics display in the middle of the line at the bottom (only if
configuration mode is deactivated).
The error message disappears again as soon as the error has been corrected.
Error message
Cause(s)
Remedy
E10
Slave not activated
The slave was detected in the system
but not activated by the master.
Detected slave profile does not
correspond to the projected slave profile
and the master is in the "protected
mode".
► Check slave profile:
[Menu] > [Slave Info]:
► Connect slave with the right profile.
► Project slaves again:
[Menu] > [Quick Setup]:
E11
Slave not present
Slave is indicated in the "list of projected
slaves" LPS but not detected on the AS-
i master.
► Check slave connections.
► Connect slave again.
E12
Slave not projected
Slave was detected on the AS-i bus but
is missing in the "list of projected
slaves" LPS.
► Project slaves again:
[Menu] > [Quick Setup]:
E13
Periphery fault detected
E14
Safety slave alert
Error message not active at present.
E15
CTT1 analog protocol failure
Error message not active at present.
E20
ASI Power Fail
The master is in the "protected mode"
and detects that the AS-i voltage supply
is not higher than 28 V.
This message is only generated if at
least one slave is projected.
► Check AS-i voltage supply on the
master and replace, if necessary.
E21
No slave detected
The master is in the "protected mode"
and detects that no slave is connected
to the AS-i bus.
This message is only generated if at
least one slave is projected.
► Check slave connections.
► Check AS-i line.