ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Menu
Main menu [Master Setup]
105
9.7
Main menu [Master Setup]
Set master operating modes
Menu tree
Description
Master Setup
AS-i Master 1
Master setup AS-i master 1
Master Setup
AS-i Master 1
Config all
AS-i master 1: configure all (password level 1 required)
Requirements:
- Operating mode = configure
- No slave with the address 0 on the bus
>
Safety query: "Are you sure?"
► After [OK]:
>
The controllere checks all connected slaves (only on this
master) and enters them as "projected" in its table.
>
The mode remains "configure".
Master Setup
AS-i Master 1
Operation Mode
AS-i master 1: operating mode (password level 1 required)
→ page
>
Display of the current setting
Master Setup
AS-i Master 1
Operation Mode
Protect. Mode
Operating mode "protected":
>
LED [PROJ] goes out.
>
Changes of the slaves are detcted (LED [CONF/PF]
lights). Slaves with another projected profile are not
activated.
Master Setup
AS-i Master 1
Operation Mode
Config. Mode
Operating mode "configure":
>
LED [PROJ] lights.
>
Changes of the slaves are detected (LED [CONF/PF]
lights). All connected slaves are active.
Master Setup
AS-i Master 1
Autoaddr. Mode
AS-i master 1: "Automatic addressing" mode (password level 1
required)
>
Display of the current setting
► Scroll between ON and OFF with [▲] or [▼]
► Adopt with [OK].
Automatic addressing ON:
Permits the replaced slave to be assigned the address of
the old slave in the protected mode (default)
Automatic addressing OFF:
The replaced slave must be manually set to the right
address.