Function
GLR
Library
CRxxxx.LIB
Function symbol
Purpose
synchro-controller
Parameter
Function input
Function
outputs
Description
The synchro-controller is a controller with PID behaviour.
The values entered at function inputs KP and KD are internally
divided by 10 so that a finder grading can be achieved (e.g. KP
= 17 corresponds 1.7)
The manipulated variables Y1 and Y2 are already normed to
the PWM function (RELOAD value = 65535). Note the inverse
logic (65535 = minimum value, 0 = maximum value).
Name
Data type Description
X1
WORD
actual value channel 1
X2
WORD
actual value channel 2
XS
WORD
preset value = reference variable
XMAX
WORD
maximum value of the preset value
KP
BYTE
constant of the P share (/10)
TN
TIME
reset time (I share)
KD
BYTE
proportional share of the D share (/10)
TV
TIME
rate time (D share)
Name
Data type Description
Y1
WORD
manipulated variable channel 1
Y2
WORD
manipulated variable channel 2