page 11
Input Test:
For the duration of the test operation (e.g. programming) the
connection needs to be connected to U
B
(supply).
For ”RUN” operation the input needs to be disconnected from
U
B
(supply).
Output Error (pin 13):
semiconductor output; short-circuit and overload protection
switching voltage
10 ... 17 V (12 V DC); 11 ... 32 V (24 V DC)
switching current
10 mA ... 100 mA
overload current
0.5 A
Relay output:
internal relay output
used in series with (max. 12 outputs the power supply of which
is interrupted on detection of an error by hardware or user
program
On principle, the unit should be switched load-free.
switching current
100 mA ... 15 A
overload current
20 A
no. of switching
operations (load-free)
≥
10
6
response time
≤
3 ms
Housing drawing: