page 84
Function outputs
Description
The function SLAVE_8_CONFIG sets or reads the I/O
configuration parameters of the 8-channel modules from ifm.
The requested configuration is set with the parameters. To
check the execution of the function the inputs READ or WRITE
should remain set until the function output CFG_RESULT has
the value 1. If the data have not yet been updated or if they
cannot be read or written, the function output CFG_RESULT
has the value 0.
The parameters can be assigned to the function during the run
time of the application program. A function block is not
necessary for each node.
The configuration data for the I/O module only become active in
the state "pre-operational". If the configuration is performed in
the state "operational", the new settings do not become valid
before passing into the mode "pre-operational" -> "operational".
Name
Data type
Description
CFG_RESULT BYTE
1 = The configuration has been read
or written successfully.
2 = The configuration has not yet
been read or written.
CHANNEL_1_
BYTE
Current configuration parameters for
channel 1
CHANNEL_2_
BYTE
Current configuration parameters for
channel 2
CHANNEL_3_
BYTE
Current configuration parameters for
channel 3
CHANNEL_4_
BYTE
Current configuration parameters for
channel 4
CHANNEL_5_
BYTE
Current configuration parameters for
channel 5
CHANNEL_6_
BYTE
Current configuration parameters for
channel 6
CHANNEL_7_
BYTE
Current configuration parameters for
channel 7
CHANNEL_8_
BYTE
Current configuration parameters for
channel 8
Summary of Contents for ecomat 100 R 360 Series
Page 1: ...System manual ecomat 100 type R 360 ...
Page 14: ...page 14 ...
Page 26: ...page 26 ...
Page 86: ...page 86 ...
Page 100: ...page 100 ...
Page 126: ...page 126 ...
Page 146: ...page 146 ...
Page 162: ...page 162 ...
Page 163: ...page 163 Annex 2 Wiring Annex 2 1 Type CR0015 ...
Page 164: ...page 164 Annex 2 2 Type CR0016 ...
Page 165: ...page 165 Annex 2 3 Type CR0017 ...
Page 166: ...page 166 Annex 2 4 Type CR0501 ...