SmartPLC SafeLine with PROFIBUS slave interface
224
Message
Type
Corrective measures
CODESYS: invalid FB parameter "ASi_Master":
currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Warning
► Check setting of the parameter "ASi_Master"
CODESYS: multiple use of an AS-i address:
currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Warning
► Check addressing of the AS-i slaves
CODESYS: FB parameter "ASi_SlaveAdr" in
invalid range: currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Warning
► Check setting of the parameter "ASi_SlaveAdr"
Simultaneous activation of both help signals of a
safe AS-i output module: currDev=%s;
currDiagState=%s; prevDiagState=%s;
addr1=%s; addr2=%s
Warning
► Check program code
CODESYS: FB parameter "ASi_SlaveAdr" refers
to a non configured AS-i address: currDev=%s;
currDiagState=%s; prevDiagState=%s;
addr1=%s; addr2=%s
Warning
► Check configuration of the AS-i network
► Check setting of the parameter "ASi_SlaveAdr"
CODESYS: too many instances of
"SF_OUTcontrol_ASi" created: currDev=%s;
currDiagState=%s; prevDiagState=%s;
addr1=%s; addr2=%s
Warning
► Check configuration of the AS-i network
► Check the number of the created logical devices for
virtual control slaves