SmartPLC SafeLine with PROFIBUS slave interface
213
Diagnostic structure
41462
In the compatibility mode AC1305/06/26, the AC412S has the following diagnostic structure:
Byte
Content
Meaning
0
Station status 1
Standard diagnostics (
→ Note)
1
Station status 2
2
Station status 3
3
Station number DP master
4
Manufacturer ID (high byte) 0x04
5
Manufacturer ID (low byte ) 0xD8
6
Length of the extended diagnostics (0x3A)
Header of the extended diagnostics
7
Status type: Status manufacturer-specific
8
Slot number (0x04)
9
0
10, 11
Master flags
Diagnostics AS-i Master 1 S/A and
B slaves
→
Master flags
(
→ S.
→
Mapping of the AS-i slave addresses
(
→ S.
12...19
LDS: list of detected slaves
20...27
LCE: list of configuration errors
28...35
LPF: list of peripheral faults
36, 37
Master flags
Diagnostics AS-i Master 2 S/A and
B slaves
→
Master flags
(
→ S.
→
Mapping of the AS-i slave addresses
(
→ S.
38...45
LDS: list of detected slaves
46...53
LCE: list of configuration errors
54...61
LPF: list of peripheral faults
62...67
reserved
reserved
Via the device parameter "Extended PROFIBUS Diag." the user can set whether only the
standard diagnostics (bytes 0...5) or the extended diagnostics (bytes 0...67) are used.
For information regarding the device parameters:
→
Parameter data: compatibility mode
AC1305/06/26
(