SmartPLC SafeLine with PROFIBUS slave interface
143
8.7
Set the Profibus interface
41431
Detailed information on how to configure the PROFIBUS network:
→ operating instructions of
the PROFIBUS master
To integrate the device into a PROFIBUS network:
1 Set the interface parameters
►
>
>
►
Set the interface parameters (→
Configure the PROFIBUS interface
).
2 Integrate device into PROFIBUS project using the GSD file
►
Copy the GSD file of the device to the PC/laptop with the PROFIBUS configuration software (→
Download GSD
file
►
Load the device into the device library of the PROFIBUS configuration software by means of the GSD file
(→ operating instructions of the PROFIBUS configuration software).
►
Integrate the device into the PROFIBUS project.
3 Set the device parameters, fieldbus modules and system behaviour
►
Set the following parameters in the PROFIBUS configuration software:
– Device-specific parameters (→
Device-specific parameters
– PROFIBUS modules (→
PROFIBUS modules: compatibility mode AC14
►
Set the system behaviour in the PROFIBUS configuration software (e.g. watchdog)
4 Activate configuration
►
Save and load the configuration to PROFIBUS controller (download).
►
Start the PROFIBUS controller.
>
The device has been integrated into PROFIBUS network (→ Status LED of the PROFIBUS interface).
5 Display the set configuration on device
►
>
>
►
Select [Profibus data] tab.
>
The page shows the saved configuration.
>
8.8
Setup of the configuration interface
41410
To set up the EtherNet configuration interface (X3):
►
>
►
Select [IP setup] tab.
►
Set the interface parameters (→
Notes on IP settings
(→ S.
)).