SmartPLC SafeLine with PROFIBUS slave interface
130
7.7.4
Safety: FSoE
42249
The menu page [FSoE] provides access to the information about the status of the fail-safe
communication via EtherCAT (FSoE).
>
Display the status of the connection to FSoE slaves
42231
To display the status of the connection to an FSoE slave:
1 Select menu page
►
>
►
Select tab [FSoE-Slaves].
2 Display the status of the connection to an FSoE slave
>
Menu page shows list with the following information (per FSoE connection):
Name
Description
Possible values
Status LED
Status display of the connection
Connection interrupted
Connection established
[Connection-ID]
ID of the FSoE connection
1...65535
Event
Description of the event
The menu page shows information about 32 FSoE connections.
>
Display the status of the fail-safe cross networking
42234
To display the status of the fail-safe cross networking to the other AC412S:
1 Select menu page
►
>
►
Select tab [FSoE-Slaves].
2 Display the status of the connection to an FSoE slave
>
Menu page shows list with the following information (per Safety NetVar connection):
Name
Description
Possible values
Status LED
Status display of the connection
Connection interrupted
Connection established
[Connection-ID]
ID of the FSoE connection
1...65535
Event
Description of the event
The menu page shows information about 32 FSoE connections.