SmartPLC SafeLine with PROFIBUS slave interface
116
Display PROFIBUS data
41416
To display the PROFIBUS data:
1 Select the menu page
►
>
>
►
Select [Profibus data] tab.
2 Display PROFIBUS data
>
Page shows the following information:
Designation
Description
Possible values
[Profibus address]
Displays the Profibus address
3 ... 126
[Profibus baud rate]
Displays the transmission rate of
the PROFIBUS interface
[Unknown]
Device is not connected to the
PROFIBUS master
[9.6 Kbits/s]
...
[12 Mbits/s]
Baud rate
[Analog. channels/I-slave]
Number of analogue channels per
projected input slave
[Unknown]
Device is not connected to the
PROFIBUS master
[1 channel
per A/B]
1 channel per A/B slave
OR:
channels 1 + 3 per single slave
[1 channel]
1 channel per single slave
OR:
1 channel per A slave
[2 channels]
2 channels per single slave
OR:
2 channels per A slave
[4 channels]
4 channels per single slave
OR:
2 channels per A/B slave
[Analog. channels/O-slave]
Number of analogue channels per
projected output slave
→ [Analog. channels/I-slave]
[Failsafe state]
Behaviour of the AS-i outputs in
case of an interrupted PROFIBUS
connection
[Clear output]
switch off AS-i outputs
[Hold output]
hold AS-i outputs on the last value
[Parameter download]
Transmission of the parameter
data of the AS-i slaves to the
device
Parameters are not downloaded, i.e. AS-i slaves
are activated with the parameters set in the
device.
Each time the PROFIBUS connection is
established the AS-i slave parameters are loaded
onto the device from the PROFIBUS controller,
activated in the slaves and stored non-volatilely.
[Profivbus alarms]
Transmission of Profibus alarms to
the PROFIBUS controller
No PROFIBUS alarms are sent.
PROFIBUS alarms are triggered in the
PROFIBUS master if there is a fault on the
device.
[Swap IO]
Swap of the nibbles in the byte
(only applies to digital data in slots
1...4)
No swap of assignment of the slave nibbles in the
byte.
Swap of assignment of the slave nibbles in the
byte.
>
Display the module configuration
41434
To display the current module configuration: