Mounting
Content
Install device ...................................................................................................................................... 28
34058
>
4.1
Install device
42302
The device must only be installed, connected and put into operation by a qualified electrician as the
safe function of the device and machinery is only guaranteed when installation is correctly carried out.
The installation and connection must comply with the applicable national and international standards.
Responsibility lies with the person installing the device.
► Fix the device onto a 35 mm raised rail.
► Vertical installation (upright).
► Adhere to a minimum distance of 30 mm between the ventilation holes (perforated sheet) and
other parts.
► Maximum operating distance: 2000 m above sea level
► The protection rating of the device is IP 20. The installation must take place in a control cabinet
with at least IP 54 protection.
► Lay the cables in a cable duct.
► Keep the installation space of the device free from electrically-conductive particles.
Ensure a condensation-free environment. Avoid excessive dust, vibration and shock. The air
circulation through the vents must not be impeded. Installation in environments with ionising
radiation is not permitted.
Avoid installation in direct vicinity of frequency inverters or other interfering sources.