SmartPLC SafeLine with PROFIBUS slave interface
225
OSC messages: System (safety)
42324
Message
Type
Corrective measures
Overvoltage on the internal supply detected:
tmn=%s; ln=%s; p1=%s; p2=%s
Warning
► Check voltage supply of the device and replace, if
necessary
Undervoltage detected on the internal supply:
tmn=%s; ln=%s; p1=%s; p2=%s
Warning
► Check voltage supply of the device and replace, if
necessary
The internal device temperature has exceeded
the warning threshold of 78°C: tmn=%s; ln=%s;
p1=%s; p2=%s
Warning
► Check thermal conditions of the system environment
The internal device temperature has exceeded
the error threshold of 85°C: tmn=%s; ln=%s;
p1=%s; p2=%s
Warning
► Check thermal conditions of the system environment
The internal device temperature has fallen below
the error threshold of -5°C: tmn=%s; ln=%s;
p1=%s; p2=%s
Warning
► Check thermal conditions of the system environment
Error in the file system (0x4045): Please contact
the ifm service centre: tmn=%s; ln=%s; p1=%s;
p2=%s
Error
► Note the message and contact the ifm service centre.
Error in the file system (0x4043): Please contact
the ifm service centre: tmn=%s; ln=%s; p1=%s;
p2=%s
Error
► Note the message and contact the ifm service centre.
Short circuit on a local output: tmn=%s; ln=%s;
p1=%s; p2=%s
Error
► Check connections of the local I/O interface.
Undervoltage or overvoltage detected on the
internal supply: tmn=%s; ln=%s; p1=%s; p2=%s
Error
► Note the message and contact the ifm service centre.
Overvoltage detected on the external supply:
tmn=%s; ln=%s; p1=%s; p2=%s
Error
► Check voltage supply of the device and replace, if
necessary
Undervoltage detected on the external supply:
tmn=%s; ln=%s; p1=%s; p2=%s
Error
► Check voltage supply of the device and replace, if
necessary
The operating mode of the safe PLC was
changed (tmn=%s; ln=%s; p1=%s; p2=%s)
Note
not necessary
The use of safe AS-i output slaves requires at
least 5 active AS-i slaves in the network.
Error
► Configure at least 5 AS-i slaves in the network.
System error:
BIT_ADC_DETERMINATION_ERR_2; tmn=%s;
ln=%s; p1=%s; p2=%s
Error
► Note the message and contact the ifm service centre.
System error:
BIT_ADCVOLT_INIT_HNDL_ERR_0; tmn=%s;
ln=%s; p1=%s; p2=%s
Error
► Note the message and contact the ifm service centre.
System error:
BIT_ADCVOLT_INIT_STRT_ERR_0; tmn=%s;
ln=%s; p1=%s; p2=%s
Error
► Note the message and contact the ifm service centre.
System error: BIT_ALLOC_SFB_ERR_1;
tmn=%s; ln=%s; p1=%s; p2=%s
Error
► Note the message and contact the ifm service centre.
System information:
BIT_ASI_ADD_INP_SLAVE_INFO_2; tmn=%s;
ln=%s; p1=%s; p2=%s
Note
► Note the message and contact the ifm service centre.
System information:
BIT_ASI_ADD_OUT_SLAVE_INFO_2; tmn=%s;
ln=%s; p1=%s; p2=%s
Note
► Note the message and contact the ifm service centre.
System warning:
BIT_ASI_CANT_ADD_IN_WARN_2; tmn=%s;
ln=%s; p1=%s; p2=%s
Warning
► Note the message and contact the ifm service centre.
System warning:
BIT_ASI_CANT_ADD_OUT_WARN_2; tmn=%s;
ln=%s; p1=%s; p2=%s
Warning
► Note the message and contact the ifm service centre.