Location 147: Auto-test Delay
Set the value required for how often a test report is required
Location 148: Number of rings before answer (805 Only)
This is the number of times the phone line must ring before the system will pickup and answer.
By default this is set to 15. This means the system will pick up the call on the 16
th
ring.
Location 149: Keypad Buzzer Options
There are two conditions which will cause the keypad to beep and give an alert of the condition.
Location 150: Hardware tamper enable
This is to enable what tampering would be monitored.
Value
Telephone line
Siren Tamper
Box Tamper
0
No
No
No
1
Yes
No
No
2
No
Yes
No
3
Yes
Yes
No
4
No
No
Yes
5
Yes
No
Yes
6
No
Yes
Yes
7
Yes
Yes
Yes
Location 151: Dial Attempts (805 Only)
The number of times the system will try and dial if communication fails.
By default this is set to 4.
Location 152 to 155: Secondary Communicator Account Code (805 Only)
For dual reporting discussed earlier this is the second account code if needed.
Location 156: Secondary Communicator Format (805 Only)
The same list applies as in location 47.
Location 157: Communication Delay
The amount of time the system will wait before sending a signal to the monitoring company and if a valid
code is entered, the signal will not be sent. This does not apply to the following:
Duress
Any Panics
Keypad Medical
Keypad Fire
Zone Programmable Outputs
Value Delay
0
Reports every 24 hours
1
Reports every 48 hours
6
Reports every 7 days
Value
Action
0
No Beep
1
Beep on trouble
2
Beep on successful communication
3
Beep on trouble condition and successful communication