I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
73
2.26. $AACnP
Description:
This command is used to read the PWM step value of a specific
channel.
Syntax:
$AACnP[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be read (00 to FF
)
Cn
Specifies the channel to be read
P
The command to read the PWM step value
Response:
Valid Command:
!AA(Data)[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
(An invalid command is returned if the specified
channel is incorrect)
AA
The address of the responding module (00 to FF)
(Data)
The PWM step value (0001 to FFFF)
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.