Examples:
Command:
$01C0F500000
Response:
!01500000
Sets the frequency value for PWM channel 0 of module 01 to 500
KHz and returns the actual frequency of 500 KHz. The duty cycle
value will be automatically set to 50.0%.
Command:
$01C2F340000
Response:
!01333333
Sets the frequency value for PWM channel 2 of module 01 to 340
KHz and returns the actual frequency of 333333 Hz. The duty cycle
value will be automatically set to 33.3%.
Related Commands:
Section 2.22 $AACnF
Note:
After using the $AACnF(Data) command, the duty cycle value will be
automatically reset to 50.0%.