I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
130
2.55. ~AATnn
Description:
This command is used to set the timeout value for the software INIT.
Syntax:
~AATnn[CHKSUM](CR)
~
Delimiter character
AA
The address of the module to be set (00 to FF)
T
The command to set the timeout value for the software
INIT.
nn
Two hexadecimal digits representing the timeout value
in seconds. The max. timeout value is 60 seconds.
When changing the Baud Rate and checksum settings
without altering the position of the INIT* pin, the ~AAI
and %AANNTTCCFF commands should be sent
consecutively and the time interval between the two
commands should be less than the software INIT
timeout value. If the software INIT timeout value is 0,
then the Baud Rate and checksum settings cannot be
changed using software only. The power-on reset value
of the Software INIT timeout is 0.
Response:
Valid Command:
!AA[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
The address of the responding module (00 to FF)