I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
131
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.
Examples:
Command:
~01I
Response:
!01
Sets the software INIT of module 01 and returns a valid response.
Command:
%0101500700
Response:
?01
Attempts to change the Baud Rate of module 01 to 19200 without
first altering the position of the INIT* pin. The module returns an
invalid response because the software INIT timeout value is 0.
Command:
~01T10
Response:
!01
Sets the software INIT timeout value of module 01 to 16
seconds and returns a valid response.