I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
143
M-7015/15P, M-7033/33D
Response
00
Address
1 Byte
1 to 247
01 Function
code 1
Byte
0x46
02
Sub function code
1 Byte
0x06
03 Reserved
1
Byte
0x00
04
Baud Rate
1 Byte
0: OK
Others: error
05 Reserved
1
Byte
0x00
06
Parity
1 Byte
0: OK
Others: error
07 Reserved
1
Byte
0x00
08
Mode
1 Byte
0: OK
Others: error
09 ~
10
Reserved
2 Bytes
0x00 0x00
Note
: The new Baud Rate and protocol will be effective after the
next power-on reset.
Error Response
00
Address
1 Byte
1 to 247
01 Function
code 1
Byte
0xC6
02
Exception code
1 Byte
03: The Baud Rate or
mode is out of range,
reserved bytes should be
filled with zeros, or an
incorrect number of bytes
were received