I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
47
2.13. $AA6NN
Description:
This command is used to reset the DI counter of a specific channel.
Syntax:
$AA6N[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be reset (00 to FF
)
6
The command to reset the DI counter
NN
A two-digit hexadecimal value, where bit 0 corresponds
to channel 0, bit 1 corresponds channel 1, etc. When
the bit is 0, it means that the channel is inactive, and 1
means that the channel has been reset.
Response:
Valid Command:
!AAVV[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
(An invalid command is returned if the specified
channel is incorrect)
AA
The address of the responding module (00 to FF)
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.