3.4. M-7088 Address Mappings
Address
Description
Attribute
00001 ~
00008
PWM status
0: Stopped
1: Started
R/W
00065 ~
00072
Overflow of DI counter, write 1 to
clear
R/W
00225 ~
00232
DI counter status
0: Disabled
1: Enabled
R/W
00257 Protocol
0: DCON
1: Modbus RTU
R/W
00260
Modbus Host Watchdog mode
0: The same as I-7000 series modules
1: The AO and DO command will clear
Host Watchdog timeout status
R/W
00261 Host
Watchdog
0: Disabled
1: Enabled
R/W
00266
Clear all DI counters
W
00270
Host Watchdog timeout status, write 1 to
clear the Host Watchdog timeout status
R/W
00278 DI
active
0: Inverse
1: Normal
R/W
00289
Save all PWM configurations into
EEPROM, write 1 to save
W
00865 ~
00872
PWM mode
0: Burst mode
1: Continuous mode
R/W