I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12
63
2.21. $AACnD(Data)
Description:
This command is used to set the duty cycle value for a specific
channel.
Syntax:
$AACnD[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be set (00 to FF)
Cn
Specifies the channel to be set
D
The command to set the duty cycle value
(Data)
The duty cycle value for the specified channel (00.1 to
99.9)
Response:
Valid Command:
!AA(Data)[CHKSUM](CR)
InValid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
The address of the responding module (00 to F
F)
(Data)
The actual duty cycle value for the specified channel
(00.1 to 99.9)
There will be no response if the command syntax is incorrect, there
is a communication error, or there is no module with the specified
address.