Environment requirements without redundant ac power
Ensure that your environment falls within the following ranges if you are not
using redundant ac power.
Table 7. Physical specifications
Environment
Temperature
Altitude
Relative
humidity
Maximum wet
bulb
temperature
Operating in
lower altitudes
10°C to 35°C
(50°F to 95°F)
0 m to 914 m
(0 ft to 3000 ft)
8% to 80%
noncondensing
23°C (73°F)
Operating in
higher altitudes
10°C to 32°C
(50°F to 90°F)
914 m to 2133 m
(3000 ft to 7000
ft)
8% to 80%
noncondensing
23°C (73°F)
Turned off
10°C to 43°C
(50°F to 109°F)
0 m to 2133 m
(0 ft to 7000 ft)
8% to 80%
noncondensing
27°C (81°F)
Storing
1°C to 60°C
(34°F to 140°F)
0 m to 2133 m
(0 ft to 7000 ft)
5% to 80%
noncondensing
29°C (84°F)
Shipping
-20°C to 60°C
(-4°F to 140°F)
0 m to 10668 m
(0 ft to 34991 ft)
5% to 100%
condensing, but
no precipitation
29°C (84°F)
Environment requirements with redundant ac power
Ensure that your environment falls within the following ranges if you are using
redundant ac power.
Table 8. Environment requirements with redundant ac power
Environment
Temperature
Altitude
Relative
humidity
Maximum wet
bulb
temperature
Operating in
lower altitudes
15°C to 32°C
(59°F to 90°F)
0 m to 914 m
(0 ft to 3000 ft)
20% to 80%
noncondensing
23°C (73°F)
Operating in
higher altitudes
15°C to 32°C
(59°F to 90°F)
914 m to 2133 m
(3000 ft to 7000
ft)
20% to 80%
noncondensing
23°C (73°F)
Turned off
10°C to 43°C
(50°F to 109°F)
0 m to 2133 m
(0 ft to 7000 ft)
20% to 80%
noncondensing
27°C (81°F)
Storing
1°C to 60°C
(34°F to 140°F)
0 m to 2133 m
(0 ft to 7000 ft)
5% to 80%
noncondensing
29°C (84°F)
Shipping
-20°C to 60°C
(-4°F to 140°F)
0 m to 10668 m
(0 ft to 34991 ft)
5% to 100%
condensing, but
no precipitation
29°C (84°F)
Preparing your environment
The following tables list the physical characteristics of the SAN Volume Controller
2145-CG8 node.
48
SAN Volume Controller: Model 2145-CG8 Hardware Installation Guide
Summary of Contents for SAN Volume Controller 2145-CG8
Page 6: ...vi SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 8: ...viii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 28: ...xxviii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 34: ...6 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 72: ...44 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 100: ...72 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 102: ...74 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 104: ...76 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 109: ......
Page 110: ...Part Number 31P1669 Printed in USA GC27 3923 02 1P P N 31P1669...