Installing the Enterprise Server H50 CPU Drawer Into A Rack Unit
Install the Rails and Mounting Hardware for the CPU Drawer
Notes:
1. The Enterprise Server H50 CPU Drawer has two service positions. One is with
the drawer pulled out the front of the rack and the other is with the drawer pulled
out the rear of the rack.
2. Two stabilizers are required to service the Enterprise Server H50 CPU Drawer.
One must be installed at the bottom front of the rack unit, and the other at the
bottom rear of the rack unit. Both must be installed prior to servicing the Enter-
prise Server H50 CPU Drawer.
3. The Enterprise Server H50 CPU Drawer must be installed in the topmost position
of the rack unit, or have another drawer unit in the position immediately above it
to prevent the drawer from tipping out of the rack unit while in the service posi-
tion.
CAUTION:
The stabilizer must be firmly attached to the bottom front of the rack to prevent
the rack from turning over when the drawers are pulled out of the rack. Do not
pull out or install any drawer or feature if the stabilizer is not attached to the
rack.
CAUTION:
The stabilizer must be firmly attached to the bottom rear of the rack to prevent
the rack from turning over when the drawers are pulled out of the rack. Do not
pull out or install any drawer or feature if the stabilizer is not attached to the
rack.
Note: Racks have EIA numbers visible from the rear that go from 1 (at the bottom)
to 32 (at the top). The lowest EIA number completely occupied by a drawer
is said to be that drawer's EIA position. Therefore, the rail surface that a
drawer sets upon is approximately in line with the lower edge of the EIA posi-
tion for that drawer. An EIA number is also used in identifying cables
attached to that drawer. The Enterprise Server H50 CPU Drawer occupies 8
EIA units. This procedure is for installation in the topmost position in the rack
unit.
1. Install one (1) nut clip on hole 2 from the top on each side at the front of the
rack.
2. Install one (1) nut clip on hole 15 and another on hole 17 from the top on each
side at the rear of the rack.
7-4
RS/6000 Enterprise Server Model H50 Installation and Service Guide
Summary of Contents for RS/6000 H50
Page 1: ...RS 6000 Enterprise Server Model H50 IBM Installation and Service Guide SA38 0547 00...
Page 16: ...xvi RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 30: ...1 12 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 131: ...Chapter 3 Error Code to FRU Index 3 51...
Page 160: ...5 18 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 245: ...Chapter 8 Parts Information Chapter 8 Parts Information 8 1...
Page 290: ...B 4 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 305: ...expect 8 r or 7 r or 6 r or 4 r or 3 r delay 2 done Appendix C Modem Configurations C 15...
Page 312: ...C 22 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 316: ...D 4 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 324: ...X 8 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 326: ...X 10 RS 6000 Enterprise Server Model H50 Installation and Service Guide...