125
Figure 59: Test Connector
2. Check for resistances shown in Figure 60.
Twinax Y Test
A twinax Y (P/N 8642550) is shown in Figure 61.
Note: All cabling system connectors are equipped with shorting bars that
function as the switches in the schematic. The contacts are open when the
connector is plugged in.
Figure 60: IMD or Direct-Connect Cable Check
Resistance Measurement
Measure Resistance
From
Impedance Matching
Device
Direct Connect Cable
Phase A to green
18 to 22
W
< 1
W
Phase B to red
18 to 22
W
< 1
W
Phase A to B
> 100 k
W
> 100 k
W
Phase A to shield
> 100 k
W
> 100 k
W
Phase B to shield
> 100 k
W
> 100 k
W
Twinax shield to
cabling system shield
< 1
W
< 1
W
Red
Orange
Black
Shield
Red
Green
Orange
Black
Green
55E1I036
Summary of Contents for 5500-01E
Page 1: ...S05J 4934 00 5500 Express IP Control Unit Planning Installation and Maintenance Guide...
Page 2: ......
Page 3: ...S05J 4934 00 5500 Express IP Control Unit Planning Installation and Maintenance Guide...
Page 16: ...xvi Planning Installation and Maintenance Guide...
Page 48: ...Chapter 2 Planning Your Installation 48 Planning Installation and Maintenance Guide...
Page 144: ...144 Planning Installation and Maintenance Guide...
Page 145: ...Appendix A 145...
Page 146: ...146 Planning Installation and Maintenance Guide...
Page 147: ...Appendix A 147...
Page 148: ...148 Planning Installation and Maintenance Guide...
Page 149: ...Appendix A 149...
Page 150: ...150 Planning Installation and Maintenance Guide...
Page 151: ...Appendix A 151...
Page 152: ...152 Planning Installation and Maintenance Guide...
Page 153: ...Appendix A 153...
Page 154: ...154 Planning Installation and Maintenance Guide...
Page 155: ...Appendix A 155...
Page 156: ...156 Planning Installation and Maintenance Guide...
Page 157: ...Appendix A 157...
Page 158: ...158 Planning Installation and Maintenance Guide...
Page 164: ...164 Planning Installation and Maintenance...
Page 184: ...Glossary 184...
Page 188: ...Index 4...
Page 191: ......