4.3 Building of SIO communication network (SIO communication)
4.3.1 Wiring
(1) Basic
Item Contents
Number of connecting units
16 axes max. (Depends on the operation mode. Refer to “1.4 Features”)
Communication cable length
Total cable length 100m or shorter
Communication cable
Two-paired twisted pair shielded cable
Terminal resistor
Recommended cable: Taiyo Electric Wire & Cable
CAUTION
1. Provide a communication path via a bus connection, and be sure to connect a terminal resistor at the
end. A terminal resistor is incorporated into the gateway unit side, therefore, it is unnecessary to connect
it.
2. The communication cable should be supplied by customer. If the recommended communication cable
is not used, use an electric wire size AWG22.
(2) Link connection for PCON-SE, ACON-SE
Gateway unit
(Incorporating
terminal resistor)
e-CON connector (AMP made 4-1473562-4: Green)
e-CON connector (AMP made 3-1473562-4: Orange)
Junction (AMP made 3-1473574-4:)
Recommended brand HK-SB/20276 × L 2P ×
AWG22
SIO communication
main line
First axis
Second axis
n
th
axis
Controller link cable
CB-RCB-CTL002
Terminal resistor
R=220
Ω
1/4W
Summary of Contents for CC-Link
Page 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition ...
Page 4: ......
Page 10: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit ...
Page 12: ...8 2 2 External dimension drawing Mounting dimension ...
Page 78: ...74 ...
Page 82: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7 ...
Page 84: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3 ...
Page 88: ...84 Command position No Completion position No 1 2 3 4 5 6 ...
Page 91: ...87 ...
Page 93: ...89 ...
Page 125: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP ...
Page 130: ...126 ...
Page 131: ......