![IAI CC-Link Operation Manual Download Page 19](http://html1.mh-extra.com/html/iai/cc-link/cc-link_operation-manual_604089019.webp)
15
b. Precautions regarding wiring method
Separate the communication lines for the gateway unit and the wiring for the CC-Link
communication line from high-power lines such as a cable connecting to a power circuit. (Do not
bundle together wiring for the communication lines with high-power lines or place them in the same
cable duct.)
c. Noise sources and elimination
Among the numerous noise sources, solenoid valves, magnet switches and relays are of particular
concern when building up a system. Noise from these sources can be eliminated by implementing
the measures specified below.
[1] AC solenoid valves, magnet switches and relays
Measure: Install a surge absorber in parallel with the coil.
[2] DC solenoid valves, magnet switches and relays
Measure: Install a diode in parallel with the coil. Determine the diode capacity in accordance
with the load capacity.
←
Point
Install a surge absorber to each
coil over a minimum wiring
length. Installing a surge
absorber to the terminal block or
other part will be less effective
because of a longer distance
from the coil.
In a DC circuit, connecting a diode in reverse polarity
will damage the diode, internal parts of the controller
and/or DC power supply, so exercise sufficient caution.
Summary of Contents for CC-Link
Page 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition ...
Page 4: ......
Page 10: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit ...
Page 12: ...8 2 2 External dimension drawing Mounting dimension ...
Page 78: ...74 ...
Page 82: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7 ...
Page 84: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3 ...
Page 88: ...84 Command position No Completion position No 1 2 3 4 5 6 ...
Page 91: ...87 ...
Page 93: ...89 ...
Page 125: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP ...
Page 130: ...126 ...
Page 131: ......