124
10.2.3 Abnormality of CC-Link communication
When the CC-Link communication is abnormal, C.ER (Red) on the gateway status indication LED is lit.
Further, details of communication status can be checked by RUN (Green), ERR (Red), SD (Green) and RD
(Green) on the CC-Link communication status LED. When any abnormality occurs, check the operation status
with the status indication list on the next page.
★
Check the communication status LED, and check the following depending on each status.
[1] Check if wiring for the communication line is correctly connected.
[2] Check if the gateway unit is correctly set to the PLC (master station) as a remote device of four stations.
(Note that this is not remote I/O.)
[3] Check that address settings for remote I/O and remote input and output are not duplicated.
[4] Check if the terminal resistors are correctly connected, and resistance values are correct.
[5] Check if the power line which becomes a noise source is not wired near wiring of the SIO
communication line.
Summary of Contents for CC-Link
Page 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition ...
Page 4: ......
Page 10: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit ...
Page 12: ...8 2 2 External dimension drawing Mounting dimension ...
Page 78: ...74 ...
Page 82: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7 ...
Page 84: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3 ...
Page 88: ...84 Command position No Completion position No 1 2 3 4 5 6 ...
Page 91: ...87 ...
Page 93: ...89 ...
Page 125: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP ...
Page 130: ...126 ...
Page 131: ......