62
Detail of input and output signal
Signal type
Bit
Signal
name
Pattern
No.
Contents Detail
b15
SON
0 – 4
Servo on command
b14
RES
0 – 4
Reset command
CSTR
0, 2, 3
Start command
b13
PWRT
1
Position data capturing command TEAC
b12
STP
0 – 4
Pause command
b11
HOME
0 – 4
Home return command
b10
BKRL
0, 2 – 4
Brake compulsory release
b9 JOG-
1 Jog-
command
b8 JOG+
1 Jog+
command
b7 JISL
1 Jog/inching
changeover
Control
signal 0
b6
MOD
1
Teach mode command
b8–b0
PC***
0 – 3
Command position No. is designated by
command position No.
PLC outp
ut
Command
position No.
b6–b0
ST0-ST6
4
Start position is designated by bit pattern.
b15
BALM
0 – 4
Battery voltage drop alarm
b14
ALM
0 – 4
Alarm occurring
b13
EMGS
0 – 4
On emergency stop
b12
SV
0 – 4
Operation preparation completion (Servo on
status)
b11
PEND
0, 2 – 4
Positioning completion
b11 WEND
1
Position data capturing command status
TEAC
b10
HEND
0 – 4
Home return completion
b9
RMDS
0 – 4
Operation mode status
b8
PZONE
0, 2 – 4
Position zone output monitor
b7
ZONE1
0, 4
Zone output monitor 1
b7
MODS
1
Teach mode status
Status
signal
b6
MOVE
0, 1
On moving
b8-b0
PM***
0 – 3
Completed position No. is read by binary
number.
PLC in
put
Completed
position No.
b6-b0
PE0-PE6
4
Completed position is read by bit pattern.
Summary of Contents for CC-Link
Page 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition ...
Page 4: ......
Page 10: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit ...
Page 12: ...8 2 2 External dimension drawing Mounting dimension ...
Page 78: ...74 ...
Page 82: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7 ...
Page 84: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3 ...
Page 88: ...84 Command position No Completion position No 1 2 3 4 5 6 ...
Page 91: ...87 ...
Page 93: ...89 ...
Page 125: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP ...
Page 130: ...126 ...
Page 131: ......