125
CC-Link communication status indication list
○
: Lit
●
: Unlit
◎
: Flashing
RUN
(Green)
ERR
(Red)
SD
(Green)
RD
(Green)
Operation
○
◎
◎
○
Communication is normally performed, however, CRC(*) error
frequently occurs due to noise.
○
0.4s
◎
◎
○
Baud rate or station No. has changed from baud rate for reset
release or station No. setting.
○
◎
◎
●
(Impossible status)
○
◎
●
○
Received data became CRC(*) error, and cannot respond.
○
◎
●
●
(Impossible status)
○
●
◎
○
Normal communication
○
●
◎
●
(Impossible status)
○
●
●
○
No data is transmitted to local station.
○
●
●
●
(Impossible status)
●
◎
◎
○
Polling response is performed, but refresh reception is CRC(*) error.
●
◎
◎
●
(Impossible status)
●
◎
●
○
Data to local station is CRC(*) error
●
◎
●
●
(Impossible status)
●
●
◎
○
Not link-started.
●
●
◎
●
(Impossible status)
●
●
●
○
There is no data to local station, or reception for local station is
impossible due to noise.
●
●
●
●
Data cannot be received due to disconnection. Power is shut off or
H/W is being set.
●
○
●
○
Invalid baud rate, invalid station No. setting
●
○
●
●
Invalid baud rate, invalid station No. setting
●
●
●
●
Power is shut off, or remote station power part is in fault.
*CRC: Cyclic Redundancy Check
Data error detecting method which is mostly used for synchronizing transmission
Summary of Contents for CC-Link
Page 1: ...IAI America Inc CC Link RCM GW CC Gateway Unit Operation ManualFirst Edition ...
Page 4: ......
Page 10: ...6 1 5 How to identify model RCM GW CC Basic model For CC Link Gateway unit ...
Page 12: ...8 2 2 External dimension drawing Mounting dimension ...
Page 78: ...74 ...
Page 82: ...78 Position data measurement value Present position 1 2 3 4 4 5 6 7 ...
Page 84: ...80 Speed acceleration and deceleration set value Actuator speed Speed n2 Speed n3 1 2 3 ...
Page 88: ...84 Command position No Completion position No 1 2 3 4 5 6 ...
Page 91: ...87 ...
Page 93: ...89 ...
Page 125: ...121 No 3 Axis 1 pause No 3 Axis 1 pause lamp No 3 Axis 1 STP ...
Page 130: ...126 ...
Page 131: ......