Shutting down
Chapter 8
OPERATION MANUAL
V2.3.0en/03.08.21//1.30
Immersion Cooler
43
Observe the wiring diagram.
→
Remove the
>Probe<
[67] from the thermal fluid. The minimum bending radius of the hose is 400
mm and
must never
be smaller.
Model F
(with flexible
>Probe<
[67]): Never use a bending radius of
less than 40 mm when bending the flexible
>Probe<
[67].
8.4
Draining the cooling water
This section must be observed when using water-cooled temperature control units.
8.4.1
Draining process
Pressurized cooling water connections
RISK OF INJURY
Wear your personnel protective equipment (e.g. safety goggles).
Carefully open the cooling water connection. Open slowly (1-2 signal edges) and drain the
cooling water slowly.
The building’s isolating valves are not closed
DAMAGE BY ROOM FLOODING
Close the building’s isolating valves in the cooling water supply and return lines.
For table-top models, place a collection container below the
>Cooling water outlet<
[14]
and/or
>Cooling water drain<
[15] (if any).
PROCEDURE
Temperature control units with >Cooling water drain< [15]
Close the isolating valves in the water supply on the temperature control unit (if present) and on
the building side.
Place a collecting container below the cooling water outlet [13], [14] and [15].
Open the
>Cooling water drain<
[15] and disconnect the
>Cooling water outlet<
[14] from the
water return. The cooling water will begin to drain out. Allow all the cooling water to drain out to
prevent the risk of freezing during transport and storage!
Disconnect the
>Cooling water inlet<
[13] from the water supply.
Close the
>Cooling water drain<
[15].
PROCEDURE
Temperature control units without >Cooling water drain< [15]
Close the isolating valves in the water supply on the temperature control unit (if present) and on
the building side.
Place a collecting container below the cooling water outlet [13] and [14].
Disconnect the
>Cooling water outlet<
[14] from the water return flow. The cooling water will
begin to drain out. Allow all the cooling water to drain out to prevent the risk of freezing during
transport and storage!
Disconnect the
>Cooling water inlet<
[13] from the water supply.
8.5
Packing
Always use the original packaging!
→
Summary of Contents for MPC TC 100
Page 1: ...MPC Immersion Cooler...
Page 2: ......
Page 3: ...OPERATION MANUAL MPC Immersion Cooler...
Page 4: ......
Page 6: ...OPERATION MANUAL Immersion Cooler V2 3 0en 03 08 21 1 30 6 MPC controller...
Page 10: ...OPERATION MANUAL Immersion Cooler V2 3 0en 03 08 21 1 30 10...
Page 46: ...Annex OPERATION MANUAL Chapter 9 Immersion Cooler V2 3 0en 03 08 21 1 30 46 9 Annex...
Page 47: ......