Service/maintenance
Chapter 7
OPERATION MANUAL
V2.3.0en/03.08.21//1.30
Immersion Cooler
39
7.3.2
Replacing coolant hoses
Replace defective coolant hoses
before
turning on the temperature control unit.
PROCEDURE
Drain the cooling water.
→
Replace the defective coolant hoses. Follow the instructions for the proper disposal.
→
Page 15,
section
»Proper disposal of resources and consumables«
Reconnect the temperature control unit to the building’s cooling water supply.
→
Page 25, sec-
tion
»Temperature control units with water cooling«
Restart the temperature control unit in normal mode.
7.3.3
Clean liquefier fins (air-cooled temperature control unit)
Manual cleaning
RISK OF BEING CUT ON THE LIQUEFIER FINS
Wear suitable cut-resistant gloves for cleaning work.
Depending on the ambient conditions, use cleaning equipment such as vacuum cleaners and/or
a hand brush/brush. Follow the local regulations when cleaning. Do not clean the liquefier fins
in a clean room with items like a brush and do not use a vacuum cleaner without an extra-fine
particle filter.
Cleaning using pointed or sharp-edged tools
DAMAGE TO THE LIQUEFIER FINS
Clean the liquefier fins using suitable cleaning appliances.
Make sure there is adequate ventilation (removal of waste heat, fresh air supply) for the tempera-
ture control unit, in case of
air cooling, maintain wall clearance
.
→
Page 18, section
illustrations of the cooling variants«
and
→
The liquefier fins must be cleaned (dust) from time to time as only then will the temperature con-
trol unit perform at its maximum cooling capacity.
PROCEDURE
Liquefier fins on lower surface
Switch off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Tilt the temperature control unit to its side. Make sure the cooling coil is not bent.
Clean the liquefier fins using suitable cleaning appliances. Observe the local regulations and
ambient conditions when selecting cleaning appliances.
Make sure the liquefier fins are not damaged or deformed as this will impair the air flow.
Put the temperature control unit upright immediately after cleaning the liquefier fins and wait
for
60 minutes
to allow the compressor oil to flow back.
Connect the temperature control unit to the power supply.
Switch on the temperature control unit.
7.3.4
Clean hat-type strainer (dirt trap) (water-cooled temperature control unit)
Building’s isolating valves are not closed
PROPERTY DAMAGE CAUSED BY FLOODING OF ROOMS
Close the building’s isolating valves in the cooling water supply and return lines.
For table-top models, place a collection container below the
>Cooling water drain<
[15]. Ob-
serve the wiring diagram:
→
The strainer at the cooling water inlet must be inspected and cleaned on a regular basis, depend-
ing on water quality.
Summary of Contents for MPC TC 100
Page 1: ...MPC Immersion Cooler...
Page 2: ......
Page 3: ...OPERATION MANUAL MPC Immersion Cooler...
Page 4: ......
Page 6: ...OPERATION MANUAL Immersion Cooler V2 3 0en 03 08 21 1 30 6 MPC controller...
Page 10: ...OPERATION MANUAL Immersion Cooler V2 3 0en 03 08 21 1 30 10...
Page 46: ...Annex OPERATION MANUAL Chapter 9 Immersion Cooler V2 3 0en 03 08 21 1 30 46 9 Annex...
Page 47: ......