Figure 4-11 Installing ramps
4. Raise the six leveling feet to the highest point using an adjustable wrench,
and push the cabinet to the installation position over castors. (Optional)
----End
4.2.1.2 Smart Cooling Product Transportation and Unpacking
Checking the Outdoor Unit Upon Arrival
Step 1 After the outdoor unit is delivered onsite, check the overtemperature mark.
Overtemperature marks are attached to the outer package and indicate whether
the ambient temperature during transportation exceeds the threshold. If yes, the
corresponding temperature mark background turns black, as shown in
.
Figure 4-12 Overtemperature mark
●
If none of the three marks turn black, the transportation meets requirements
and the outdoor unit can be installed after its package is removed as
instructed in
.
●
If the mark with 60 turns black, unpack the outdoor unit and open its top
cover, front panel, and left front panel. Then check whether there is trace of
liquid around the safety valve connector. If yes, replace the safety valve. If no,
install the outdoor unit. For position of safety valve, see the overtemperature
mark.
●
If the marks with 60, 65 turn black or all the marks turn black, ask Huawei to
confirm whether the unit can be used.
----End
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
104