Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
77
Menu
Parameter
Description
Default Value
Screen
>
Settings
>
Quick
Settings
>
Date &
Time
Settings
for the ACC.
current interface date
format
Date
Sets the date displayed on the
ACC.
Consistent with the
current interface date
Time
Sets the time displayed on the
ACC.
Consistent with the
current interface time
Time zone
Sets the time zone displayed
on the ACC.
Consistent with the
current interface time
zone
Home
Screen
>
Settings
>
Quick
Settings
>
System
Settings
Monitoring mode Sets the mode in which the
host computer software
monitors the precision air
conditioners.
Single mode
Energy-saving
mode
Sets the fans to rotate at a low
speed when there is no
requirement.
Off
Home
Screen
>
Maint
>
Performan
ce Maint
CW valve total
runtime,
compressor total
runtime, indoor
fan total runtime,
elec heater total
runtime,
humidifier total
runtime, cond
pump total
runtime, cond
pump run factor,
air filter total
runtime
Check or clear the total
runtime for each component.
0 h
Home
Screen
>
Maint
>
Sensor
Adjust
Supply-air temp
adj value,
return-air 1 temp
adj value,
return-air humid
adj value,
supply-water
temp adj value,
return-water
temp adj value,
cold-aisle temp
adj value,
cold-aisle humid
adj value,
hot-aisle temp
adj value,
hot-aisle humid
adj value, liquid
Sets the adjustment value of
each sensor when the detected
temperature or humidity varies
from the practical value. For
example, if the detected return
air temperature is 1°C lower
than the value detected by
other devices, set the
calibration value to 1°C.
0.0°C or 0.0% RH