Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16
Parameter Specification Setting Method
Connection mode
to
Server
.
Client: If the precision air conditioner and EMS need
to access the Internet, set
Connection mode
to
Client
.
client: This option provides functions of both
the
Server
and
Client
options.
EMS IP
address
-
Enter the actual IP address of the EMS. IP addresses of
the display panel, client EMS, and server EMS must be
unique. This parameter is configurable when
Connection
mode
is set to
Client
.
EMS port
-
It is recommended that you retain the default value
16100. If you need to change the value, enter a value as
required. This parameter is configurable when
Connection mode
is set to
Client
.
----End
3.2.8 Setting SNMP Parameters
Context
To set communications parameters, log in as the
Admin
, or
Engineer
user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a precision
air conditioner to an NMS (network management system).
One precision air conditioner supports concurrent access of up to 10 NMSs through
SNMP.
Procedure
Step 1
On the home screen, choose
Settings
>
Comm Settings
>
SNMP Settings
displayed.
Figure 3-9
Setting SNMP communications parameters