Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
14
----End
3.2.6 Setting Communications Parameters (IP Address Settings)
Context
To set communications parameters, log in as the
Admin
, or
Engineer
user.
Procedure
Step 1
On the home screen, choose
Settings
>
Comm Settings
>
IP Settings
displayed.
Figure 3-7
Setting the IP address, subnet mask, and gateway address
Step 2
Set the parameters by referring to
Table 3-4
IP address settings
Parameter
Setting Method
IP address
Set according to the actual plan
Subnet mask
Set according to the actual plan
Gateway
Set according to the actual plan
----End
3.2.7 Setting Communications Parameters (ModBus Settings)
Context
To set communications parameters, log in as the Admin or Engineer user.
If
Connection mode
is set to
Server
, one precision air conditioner can be accessed by a
maximum of two element management system (EMS) clients at the same time. If