Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
25
Figure 3-20
Teamwork topology
Table 3-7
Note for the screen
No.
Parameters
Note
1
ON/OFF/NA
On
indicates the precision air conditioner is started
and
Off
indicates the precision air conditioner is
shut down.
NA
indicates the precision air
conditioner is offline.
2
01, 02, 03
Indicates the device address.
01
is the master one
and the rest are all slave ones.
NOTE
If the master one offline, the teamwork networking failed.
3
Active/Standby
Active: properly responds to the requirement
control.
Standby: responds to the requirement control when
Active
is faulty (critical alarms, shutdown, and
offline) or
Active
cannot meet cooling
requirements.
4
Frame:
green/non-green
A device with green frame indicates the device
itself, as shown in
.
A non-green frame indicates the other device in the
group, as shown in
.
5
Ground color: red,
bright gray, dark gray
Red indicates that a critical alarm is generated, as
shown in
.
Bright gray indicates that the device is operating