Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
15
Connection mode
is set to
Client
, a precision air conditioner can be connected only to
an EMS with a specific ID address. If
Connection mode
is set to
client
, one
precision air conditioner can be accessed by a maximum of two EMS clients and connect
to an EMS with a specific ID address at the same time.
Procedure
Step 1
Choose
Settings
>
Comm Settings
>
Modbus Settings
on the home page. The page shown
in
Figure 3-8
Setting Modbus communications parameters
Step 2
Set the parameters by following instructions in
Table 3-5
Modbus parameter settings
Parameter Specification Setting Method
Protocol
Modbus RTU,
Modbus TCP
Modbus RTU: If a precision air conditioner needs to
connect to an EMS using an RS485 cable, set
Protocol
to
Modbus RTU
.
Modbus TCP: If a precision air conditioner needs to
connect to an EMS through an IP address network, set
Protocol
to
Modbus TCP
.
Baud rate
9600, 19200
Set the baud rate as required. The value should be
consistent with that at the EMS side. This parameter is
configurable when
Protocol
is set to
Modbus RTU
.
Comm
address
1–255
Set the address of the precision air conditioner. The EMS
communicates with the precision air conditioner through
this address, and the addresses of two precision air
conditioners connected to the same EMS must be unique.
This parameter is configurable when
Protocol
is set to
Modbus RTU
.
Connection
mode
Server, Client,
client
This parameter is configurable when
Protocol
is set to
Modbus TCP
.
Server: If the precision air conditioner and EMS do
not need to access the Internet (the precision air
conditioner and the EMS are in the same LAN), set